谁给全部翻译并且解释下

1.SetyourPGInterfacetoCP5611(MPI)
ConnectyourFielDPGtotheCPUwiththeMPICable
2.OpentheFolder"Ethernet"intheSimaticManagerChoosetheCPU,3whichyoureplacedandclickonthedownloadButton5.TheProgramwillASkyouforsomeSettings.Allthisshouldberight,soonlyclickonOK
6.AftertheseSTepsyoucanchangeyourPGInterfacebacktoEthernet,andthenyouhaveto
downloadallBlocks
ForthisyouopentheFolder"Blocks"intheSimaticManagerandmarkallBlocksexcept
"Systemdata"
ButbeforeyoudownloadallBlocks,youhavetostoptheCPU!!!!
MakerightmouseclickonanyBlockandpressDownload7.AfterthisyoucanstartyourCPUagain,andeverythingshouldworklikebefore
8.ButyouhavetoloadallParameterfilesintheVisualisationSystemagain
9.YoualsohavetosettheTimeontheCPU.Forthis,opentheHardwareConfigurationagain,
goonlineandmakerightmouseclickonCPUandpress"SetTimeofDay"这是更换CPU的步骤,

问题补充:
主要是步骤6和8

最佳答案

1.设置PG接口为CP5611(MPI),把PG(计算机或其他设备)用MPI电缆连接
2.在simaticmanager中打开Ethernet"选中你要替换(参数)的CPU单击“下载”按钮。
5.程序会要求你输入一些设置,因为默认的设置都是对的所以只要单击OK即可。
6.上述操作完成后你可以把PG接口改为Ethernet,然后下载所有程序块。为此你需要打开simaticmanager的blocks,然后选中除systemdata之外的所有块,但是下载之前你必须把cpu置于停止状态。确认所有的块都被选中后然后下载。
7.操作完成后你可以重启CPU,所有东西都会和从前一样。
8.但是你必须再次把参数文件上传到组态中。
9.另,你必须设置CPU中的时间。打开“硬件组态”,设为在线状态,右击(双击)CPU后选中“设置时间日期”。