显示:theuserdoesnothavetherightSToperformthisaction!
pleASechecktheassignmentofthecurrentuseroftheusergroupsinwindows.
最佳答案
参考:
Errorwhenopeningaprojectinwincc:Theuserdoesnothavetherightstoperformthisaction!
QUESTION:
IamusingPCS7/APACS+OSVersion7.0.WhenIlogontotheOperatingSystemasanAdministrator,WinCCExplorerworksfineandIcanopenmyproject.However,whenIamloggedontotheOperatingSystemasanOperatorandIattempttoopenmyprojectinWinCCExplorer,Igetthefollowingerror;"OpenWinCCproject.Theuserdoesnothavetherightstoperformthisaction!PleasechecktheassignmentofthecurrentuseroftheusergroupsinWindows".Whycan”tIopenmyprojectinWinCCExplorerwhenloggedinasOperator?
ANSWER:
InordeRTobeabletoopenaprojectinWinCCExplorerwhileloggedonasOperator,theOperatorUsermustbeamemberofthefollowingGroups:
PowerUsers
SIMATICHMI
SQLServer2005MSSQLUser$<COMPUTERNAME>$WINCC
IftheOperatorUserisnotamemberoftheSIMATICHMIandSQLServer2005MSSQLUser$<COMPUTERNAME>$WINCCGroups,thiserrorwilloccur.
参考:
htTP://support.automation.siemens.com/CN/view/en/36069522
西门子英文论坛相关讨论——
http://www.automation.siemens.com/forum/guests/PostShow.aspx?PostID=296973&language=en&PageIndex=1
提问者对于答案的评价:
谢谢