CPU314出现运行一段时间之后,就自动停止

运行了3年左右吧,出现这个问题以后换了CPU和MMC卡,还有部分AI卡件,还是出现这个问题,现在已经不知道该怎么办了?DiagnoSTicbufferofmoduleCPU314OrderNo./DEScriptionComponentVersion6ES7314-1AG14-0AB0Hardware2–––FirmwareV3.0.3BootLoaderFirmwareexpansionA25.7.5Rack:0Slot:2Serialnumber:SC-A9VH83122010Event1of500:EventID16#4358AllmodulesarereadyforoperationOperatingmode:STOP(internal)Incomingevent01:45:52.073AM07/09/1999Event2of500:EventID16#4357ModulemonitoringtimestaRTedOperatingmode:STOP(internal)Incomingevent01:45:51.439AM07/09/1999Event3of500:EventID16#4357ModulemonitoringtimestartedOperatingmode:STOP(internal)Incomingevent01:45:50.966AM07/09/1999Event4of500:EventID16#4357ModulemonitoringtimestartedOperatingmode:STOP(internal)Incomingevent01:45:50.286AM07/09/1999Event5of500:EventID16#4357ModulemonitoringtimestartedOperatingmode:STOP(internal)Incomingevent01:45:49.817AM07/09/1999…..Event500of500:EventID16#4357ModulemonitoringtimestartedOperatingmode:STOP(internal)Incomingevent01:45:49.348AM07/09/1999

最佳答案

诊断信息单一,信息内容少,不是很好判断,先建议如下处理措施:
1、程序中检查并补齐OB80、OB81、OB82、OB83、OB84、OB85、OB86、OB87、OB121、OB122,然后观察是否停机,若不停机,在STOP时肯定调用了哪个OB,找到该OB后调用该OB报警信息,查看能详细些。
2、在条件允许时,下载个空程序或小实验程序到CPU,排除程序上的问题。

3、检查柜内接地、做好信号隔离和电源隔离,排除干扰原因、排除电源引入干扰源、排除大功率/高频设备干扰。

提问者对于答案的评价:
我在看看吧,我把别的机器的CPU带程序拿过来,到别的机器,别的运行没问题,这个还是出现这个情况,就还有的DI卡件没换