CPU报警SF错误,什么原因?

设备每次停机后CPU报警SF(报警信息如下所示),重启CPU后报警消除,什么原因?怎么解决?万分谢谢!


DiagnoSTicbufferofmoduleCPU317-2DP

OrderNo./DescriptionComponentVersion
6ES7317-2AJ10-0AB0Hardware5
–––FirmwareV2.6.0
BootLoaderFirmwareexpansionA10.13.9

Rack:0
Slot:2


Serialnumber:SC-VNE203912007


Event1of10:EventID16#2943
I/OacCEsserror,writing
Parea,double-wordaccess,Accessaddress:280
RequestedOB:I/OaccesserrorOB(OB122)
PriorityclASs:12
Externalerror,Incomingevent
12:13:14.200AM09/04/1998
(Coding:16#29430C7A0030011800000000)


Event2of10:EventID16#2942
I/Oaccesserror,reading
Parea,double-wordaccess,Accessaddress:280
RequestedOB:I/OaccesserrorOB(OB122)
Priorityclass:12
Externalerror,Incomingevent
12:13:14.200AM09/04/1998
(Coding:16#29420C7A0030011800000000)


Event3of10:EventID16#2943
I/Oaccesserror,writing
Parea,double-wordaccess,Accessaddress:280
RequestedOB:I/OaccesserrorOB(OB122)
Priorityclass:12
Externalerror,Incomingevent
12:13:14.100AM09/04/1998
(Coding:16#29430C7A0030011800000000)


Event4of10:EventID16#2942
I/Oaccesserror,reading
Parea,double-wordaccess,Accessaddress:280
RequestedOB:I/OaccesserrorOB(OB122)
Priorityclass:12
Externalerror,Incomingevent
12:13:14.100AM09/04/1998
(Coding:16#29420C7A0030011800000000)

最佳答案

参见:为什么会出现“I/O访问错误”和“区域长度错误”
htTPs://suppoRT.industry.siemens.com/cs/document/78943685/为什么会出现“io访问错误”和“区域长度错误”?dti=0&lc=zh-CN

提问者对于答案评价:
谢谢!

专家置评

已阅,最佳答案正确。